VS1-12 Handcart Type Vacuum Circuit Breaker
KCISE
VS1-12 Handcart Type Vacuum Circuit Breaker
| Rated voltage: | |
|---|---|
| Rated current: | |
| Availability: | |
| Quantity: | |

The ZN63-12(VS1) high-voltage vacuum circuit breaker is an indoor switchgear device with a rated voltage of 12 kV and a three-phase AC frequency of 50 Hz. It is an electrical protection and control device used in power systems, particularly suitable for applications that require frequent operation at rated current or repeated switching of short-circuit currents.
This circuit breaker is designed as an integrated unit combining the actuator and the breaker body. It can be used in fixed installation units, or, when equipped with a dedicated trolley mechanism, it can form a withdrawable unit. Appropriate interlocks can be added to meet the requirements of fixed cabinets such as XGN2 and GG1A. At the same time, it can be coordinated with manually operated switchgear of intermediate arrangement such as KYN28A-12 (GZS1), or with fixed switchgear such as XGN.
Normal operating and installation conditions
◎ Ambient temperature: maximum temperature: + 40 ℃ minimum temperature: - 15 ℃
◎ Ambient humidity: daily average relative humidity: ≤ 95%, monthly average relative humidity: ≤ 90%, daily average vapor pressure:
≤ 2.2 × 10-3mpa monthly average vapor pressure: ≤ 1.8 × 10-3MPa
◎ Altitude: no more than 1000M
◎ The seismic intensity shall not exceed 8 degrees
◎ The place of use shall be free of dripping water, flammable and explosive hazards, chemical corrosive gases and violent vibration.

The ZN63-12(VS1) high-voltage vacuum circuit breaker is an indoor switchgear device with a rated voltage of 12 kV and a three-phase AC frequency of 50 Hz. It is an electrical protection and control device used in power systems, particularly suitable for applications that require frequent operation at rated current or repeated switching of short-circuit currents.
This circuit breaker is designed as an integrated unit combining the actuator and the breaker body. It can be used in fixed installation units, or, when equipped with a dedicated trolley mechanism, it can form a withdrawable unit. Appropriate interlocks can be added to meet the requirements of fixed cabinets such as XGN2 and GG1A. At the same time, it can be coordinated with manually operated switchgear of intermediate arrangement such as KYN28A-12 (GZS1), or with fixed switchgear such as XGN.
Normal operating and installation conditions
◎ Ambient temperature: maximum temperature: + 40 ℃ minimum temperature: - 15 ℃
◎ Ambient humidity: daily average relative humidity: ≤ 95%, monthly average relative humidity: ≤ 90%, daily average vapor pressure:
≤ 2.2 × 10-3mpa monthly average vapor pressure: ≤ 1.8 × 10-3MPa
◎ Altitude: no more than 1000M
◎ The seismic intensity shall not exceed 8 degrees
◎ The place of use shall be free of dripping water, flammable and explosive hazards, chemical corrosive gases and violent vibration.
Project | Company | Numerical value | ||
Rated voltage | kV | 12 | ||
Rated short-time power frequency withstand voltage | kV | 42 | ||
Rated lightning impulse withstand voltage (Peak) | kV | 75 | ||
Rated frequency | Hz | 50 | ||
Rated current | A | 630、 1250 | 630、1250、1600 | 1250、1600 |
Rated short-circuit breaking current
| kA | 20/25 | 31.5 | 40 |
Rated short-time withstand current | kA | 20/25 | 31.5 | 40 |
Rated short-circuit continuous current | S | 4 | ||
Rated peak withstand current | kA | 50/63 | 80 | 100 |
Rated short-circuit making current | kA | 50/63 | 80 | 100 |
Power frequency withstand voltage of secondary circuit | V | 2000 | ||
Rated breaking current of single / back-to-back capacitor bank | A | 630/400(40kA 为 by 800/400) | ||
Rated capacitor bank closing inrush current | kA | 12.5( 频率不大于 1000Hz Frequency not greater than 1000Hz) | ||
Opening time (rated voltage) | ms | ≤ 50 | ||
Closing time (rated voltage) | ms | ≤ 100 | ||
Mechanical life | 次 second | 20000 | ||
Rated current breaking times (electrical life) | 次 second | 20000 | ||
Rated short circuit current breaking times | mm | 50(40kA ≤ 30) | ||
Allowable wear cumulative thickness of moving and stationary contacts | 3 | |||
Rated closing operating voltage | V | AC110/220 DC110/220 | ||
Rated opening operating voltage | V | AC110/220 DC110/220 | ||
Rated voltage of energy storage motor | V | AC110/220 DC110/220 | ||
Rated power of energy storage motor | W | 70 | ||
Energy storage time | S | ≤ 10 | ||
Contact opening distance | mm | 11±1 | ||
Overtravel | mm | 3.5±1 | ||
Contact closing bounce time | ms | ≤ 2(40kA ≤ 30) | ||
Asynchrony of three-phase opening and closing | ms | ≤ 2 | ||
Average opening speed (contact separation ~ 6mm) | m/s | 0.9~1.2 | ||
Average closing speed (contact closing~ 6mm) | m/s | 0.4~0.8 | ||
Main circuit resistance | μΩ | ≤ 60(630A) ≤ 55(1250A) ≤ 45(1600) | ||
Contact closing pressure | N | 2000±200(20kA);2400±200(25kA); 3100±200(31.5kA);4250±250(40kA); | ||
Rated operating sequence | 分 -0.3S- 合分 -180S- 合分 Opening -0.3S-closing and opening-180S-closing and opening | |||
Project | Company | Numerical value | ||
Rated voltage | kV | 12 | ||
Rated short-time power frequency withstand voltage | kV | 42 | ||
Rated lightning impulse withstand voltage (Peak) | kV | 75 | ||
Rated frequency | Hz | 50 | ||
Rated current | A | 630、 1250 | 630、1250、1600 | 1250、1600 |
Rated short-circuit breaking current
| kA | 20/25 | 31.5 | 40 |
Rated short-time withstand current | kA | 20/25 | 31.5 | 40 |
Rated short-circuit continuous current | S | 4 | ||
Rated peak withstand current | kA | 50/63 | 80 | 100 |
Rated short-circuit making current | kA | 50/63 | 80 | 100 |
Power frequency withstand voltage of secondary circuit | V | 2000 | ||
Rated breaking current of single / back-to-back capacitor bank | A | 630/400(40kA 为 by 800/400) | ||
Rated capacitor bank closing inrush current | kA | 12.5( 频率不大于 1000Hz Frequency not greater than 1000Hz) | ||
Opening time (rated voltage) | ms | ≤ 50 | ||
Closing time (rated voltage) | ms | ≤ 100 | ||
Mechanical life | 次 second | 20000 | ||
Rated current breaking times (electrical life) | 次 second | 20000 | ||
Rated short circuit current breaking times | mm | 50(40kA ≤ 30) | ||
Allowable wear cumulative thickness of moving and stationary contacts | 3 | |||
Rated closing operating voltage | V | AC110/220 DC110/220 | ||
Rated opening operating voltage | V | AC110/220 DC110/220 | ||
Rated voltage of energy storage motor | V | AC110/220 DC110/220 | ||
Rated power of energy storage motor | W | 70 | ||
Energy storage time | S | ≤ 10 | ||
Contact opening distance | mm | 11±1 | ||
Overtravel | mm | 3.5±1 | ||
Contact closing bounce time | ms | ≤ 2(40kA ≤ 30) | ||
Asynchrony of three-phase opening and closing | ms | ≤ 2 | ||
Average opening speed (contact separation ~ 6mm) | m/s | 0.9~1.2 | ||
Average closing speed (contact closing~ 6mm) | m/s | 0.4~0.8 | ||
Main circuit resistance | μΩ | ≤ 60(630A) ≤ 55(1250A) ≤ 45(1600) | ||
Contact closing pressure | N | 2000±200(20kA);2400±200(25kA); 3100±200(31.5kA);4250±250(40kA); | ||
Rated operating sequence | 分 -0.3S- 合分 -180S- 合分 Opening -0.3S-closing and opening-180S-closing and opening | |||
The outline and installation dimensions of ordinary type and fixed sealed vacuum circuit breaker are the same 手车式 Handcart type VF1(800)
Rated current | 630 | 1250 |
Rated short-circuit breaking current | 20、25、31.5 | 20、25、31.5、40 |
Mating static contact size | Ø35 | Ø49 |
The primary phase to phase distance is 150mm, and the cabinet width is 650mm.
The outline and installation dimensions of ordinary type and fixed sealed vacuum circuit breaker are the same 手车式 Handcart type VF1(800)
Rated current | 630 | 1250 |
Rated short-circuit breaking current | 20、25、31.5 | 20、25、31.5、40 |
Mating static contact size | Ø35 | Ø49 |
The primary phase to phase distance is 150mm, and the cabinet width is 650mm.






◎ Secondary control voltage: DC220v, AC220V, DC110v, AC110V
◎ Optional configuration of secondary control:
(1) Locking device: function - to prevent closing when the secondary control power supply is not connected or lower than the technical requirements.
(2) Transition device: function - when the primary circuit is overloaded or short circuited, the overcurrent coil is electrically operated through the overcurrent relay to open the circuit breaker. Generally, three phases are added on phase A and C, and there are two kinds of overcurrent tripping: 3.5A and 5A.
(3) Undervoltage and loss of voltage release device: function - the undervoltage release is opened at the circuit breaker when the intermediate Pt voltage is less than 35% VN, and the circuit breaker can be fully opened reliably when the intermediate voltage is ≥ 85% VN; The voltage loss release cannot be fully opened when the intermediate Pt voltage is less than 35% VN, and the circuit breaker shall not be opened when the intermediate Pt voltage is ≥ 65% VN.
◎ Grounding device:
According to the width of circuit breaker distribution cabinet, it can be divided into 650 wide grounding scheme, 800 wide grounding scheme and 1000 wide grounding scheme.
◎ Electrical parameters of secondary components
Operating voltage 220V
Closing electromagnet | Opening electromagnet | Locking electromagnet | |
Loop current | 1.0A/1.7A | 0.9A/1.7A | 20mA |
Power | 220/375 | 198/375 | 4.8 |
Operating voltage 110V
Closing electromagnet | Opening electromagnet | Locking electromagnet | |
Loop current | 2.0A/3.34A | 0.8A/3.34A | 2/mA/40mA |
Power | 220/368 | 198/368 | 2.7/4.8 |
◎ Secondary control voltage: DC220v, AC220V, DC110v, AC110V
◎ Optional configuration of secondary control:
(1) Locking device: function - to prevent closing when the secondary control power supply is not connected or lower than the technical requirements.
(2) Transition device: function - when the primary circuit is overloaded or short circuited, the overcurrent coil is electrically operated through the overcurrent relay to open the circuit breaker. Generally, three phases are added on phase A and C, and there are two kinds of overcurrent tripping: 3.5A and 5A.
(3) Undervoltage and loss of voltage release device: function - the undervoltage release is opened at the circuit breaker when the intermediate Pt voltage is less than 35% VN, and the circuit breaker can be fully opened reliably when the intermediate voltage is ≥ 85% VN; The voltage loss release cannot be fully opened when the intermediate Pt voltage is less than 35% VN, and the circuit breaker shall not be opened when the intermediate Pt voltage is ≥ 65% VN.
◎ Grounding device:
According to the width of circuit breaker distribution cabinet, it can be divided into 650 wide grounding scheme, 800 wide grounding scheme and 1000 wide grounding scheme.
◎ Electrical parameters of secondary components
Operating voltage 220V
Closing electromagnet | Opening electromagnet | Locking electromagnet | |
Loop current | 1.0A/1.7A | 0.9A/1.7A | 20mA |
Power | 220/375 | 198/375 | 4.8 |
Operating voltage 110V
Closing electromagnet | Opening electromagnet | Locking electromagnet | |
Loop current | 2.0A/3.34A | 0.8A/3.34A | 2/mA/40mA |
Power | 220/368 | 198/368 | 2.7/4.8 |